HE360A,B Powered
Flow-Through
Humidifier
INSTALLATION GUIDE/OWNER’S MANUAL
69-1176-04
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
WELCOME
To the comfortable world of humidified air. When you use your Honeywell humidifier,
notice that your skin is not as dry, and that your scratchy throat and irritated nasal
passages that aggravate allergies and asthma are steadily improving.
You have also taken the first step in reducing the zapping you create when you walk on
your carpet and then touch your TV, computer, metal door knob or your pet. Your
furniture and woodwork are also benefitting from the difference that humidified air
makes.
Congratulations! You have just made a great investment in improving the comfort of
your home.
APPLICATION
This kit contains your new Honeywell HE360 Humidifier, H8908 Humidistat and all the
accessories required for installation.
How Your Humidifier Works
Your Honeywell humidifier uses the principle that vapor (evaporated water) is created
when warm air blows over a water-soaked area. As the vapor circulates, the relative
humidity rises.
Your humidity control monitors the relative humidity and activates the humidifier
accordingly. The humidifier has a water supply that dispenses water evenly over a
humidifier pad. The warm dry air, from the furnace, passes over the humidifier pad and
picks up the moist air to circulate it throughout your home.
Humidified air feels warmer and more comfortable so you may be able to lower your
thermostat heating setpoint, which saves money on your heating fuel bills. The end
result is that your humidifier gives you a comfortable environment that is also energy
efficient.
3
69-1176—04
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
Installation Accessories (Available in Installation Kit 32005847-00)
Table 1. Required Accessories
Quantity
Accessory
Illustration
20 ft (6.2m) 18 gauge, two-strand thermostat wire
THERMOSTAT WIRE
M31006
20 ft (6.2m) 1/4 in. (6.35 mm) OD feed water tubing
10 ft (3.1m) 1/2 in (12.7 mm) ID drain tubing
PLASTIC TUBING
M31007
1 bag
Connecting and mounting hardware:
Wire nuts (4)
PLASTIC RING
WIRENUT
M31009
CLAMP
No. 8 sheet metal screws (18)
Drain tube clamp
Feed tube mounting clamps (6)
Brass inserts (2)
Plastic compression rings (2)
M31020
M31012
#8 SHEET
METAL
SCREW
DRAIN TUBE CLAMP
M31015
BRASS INSERT
M31014
M31011
1
Sail switch
SAIL
SWITCH
M31008
1
H8908 Humidistat
H8909 HUMIDISTAT
OUTDOOR
HUMIDITY
SETTING
15%
TEMPERATURE
-
2
0
¡
F
-
3
0
¡
C
-
1
0
¡
F
-25 ¡C
-20 ¡C
-10 ¡C
-5 ¡C
C
20%
0
¡F
25%
+10 ¡F
+20 ¡F
30%
35%
Humidity Control
Régulateur d'humidité
40%
O
v
e
r
2
0
¡
F
Over
0
¡
M31010
1 bag
Saddle Valve Assembly:
Saddle valve and top clamp (1)
Threaded bottom clamp (1)
Bolts (2)
SADDLE VALVE
ASSEMBLY
SADDLE VALVE
RUBBER
GASKET
Rubber gasket (1)
Eyelet (1) not shown
Plastic bushing (1) not shown
TOP CLAMP
BOLTS
BOTTOM
CLAMP
M31000
69-1176—04
4
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
Required Tools
Tools required for installation include:
•
•
•
•
•
•
•
Tin snips.
Screwdriver.
Adjustable or open-end wrench.
Battery-powered Drill, punch or awl.
Level.
Work Gloves (preferably cut-resistant).
Safety Glasses.
5
69-1176—04
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
INSTALLATION
Preparing for the Installation
Be sure to identify all the required (Table 1) accessories (included) and make sure the
appropriate tools are available before beginning the installation.
Installing the Humidifier
WARNING
Hazardous Voltage
Can cause personal injury or equipment damage.
Do not cut or drill into any air conditioning or electrical accessory.
CAUTION
Sharp Edges Installation Hazard.
Can cause personal injury.
Wear gloves and safety glasses.
1. Turn off power to the air handing system at the circuit breaker.
2. Draw a level line on the plenum in the location
chosen for the humidifier. (Leveling assures optimal humidifier performance.)
3. Locate the template (form number 69-1651 included in the box).
4. Tape the template in position and trace around the template.
5. Remove the template and carefully cut the rectangular opening.
6. Disassemble the humidifier; remove the cover and take out the humidifier pad
assembly. See Fig. 1.
FEED TUBE NOZZLE
WATER
DISTRIBUTION TRAY
HUMIDIFIER
PAD ASSEMBLY
HUMIDIFIER
HOUSING
COVER
ASSEMBLY
THUMB
SCREW
M12809
Fig. 1. Disassembling humidifier.
69-1176—04
6
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
•
•
•
Select a location that cannot damage the air conditioner A-coil during installation.
Do not locate the humidifier on the furnace body.
Allow adequate clearance in front of and above the humidifier so you can easily
remove the cover to perform routine maintenance.
—
Mount the humidifier at least 3 in. (78 mm) above the furnace body to allow
adequate space for the solenoid valve and drain line.
—
Mount the humidifier in a conditioned space to prevent freezing.
Selecting Water Supply Location
•
Use either hard or soft water in the humidifier and either hot or cold water. The
water flow rate, with the humidifier running, is 3.5 gal/hr (13 liters/hr) to flush the
pad and provide moisture for evaporation.
•
Make sure that the 20 ft (6.2m) of feed water tubing provided is adequate to
connect the water supply (saddle valve) with the humidifier solenoid valve.
Locating Closest Floor Drain
•
Select location with access to a floor drain to provide drainage for air conditioner
condensation and humidifier drainage.
•
If you do not have a drain available, we recommend that you install the Honeywell
Whole House Drum or Disk Humidifier. Make sure that the 10 ft (3.1m) of drain
tubing is adequate to reach from the humidifier drain connection to the floor drain.
Selecting Location for Sail Switch
•
Select a location for the sail switch in the cold air return duct where the sail is in the
direct path of an unrestricted air stream.
—
Sail switch detects when furnace fan is operating.
•
Select a location where the air duct is at least 12 in. (305 mm) deep and 8 in. (203
mm) wide to allow operation of the sail without affecting the smooth flow of air in the
duct.
—
Airflow at the location can be vertical (up or down) or horizontal.
IMPORTANT
Mounting the S688 in warm air supply duct can reduce the sail life.
•
•
Mount the switch at least 6 in. (152 mm) upstream from an elbow or junction, and at
least 15 in.
(381 mm) downstream from an elbow or junction.
Locate the switch on the opposite side of the duct from the air entrance. (See Fig.
1-3 in S688 Installation Instructions.)
Selecting Location for Humidistat
•
Select a location for the humidistat on the return plenum or on the wall in the living
space.
—
Mounting on the return plenum is the easiest installation for the control wiring
circuit.
For return duct mounting, the humidistat should be mounted upstream from the
humidifier or bypass so that it is properly sensing the relative humidity of the living
space. Locate the control at least 8 in. (203 mm) upstream from the humidifier in the
return air duct. (See Fig 2.)
7
69-1176—04
RETURN
AL
HORIZONT
RETURN
HIGHBOY
RETURN
RETURN
DOWN
FLO
BOY
LOW
M12808B
Fig. 2. Selecting duct location for humidistat.
Locating Closest 120V Electrical Outlet
•
•
•
Select location with access to an outlet. If not available, contact an electrician to
have one installed.
Make sure that the humidifier cord is adequate to reach from the humidifier to the
outlet.
Make sure that the 20 ft (6.2m) of thermostat wire is adequate to reach from the
humidifier solenoid, to the sail switch, to the humidistat.
Installing the Humidifier
WARNING
Hazardous Voltage
Can cause personal injury or equipment damage.
Do not cut or drill into any air conditioning or electrical accessory.
CAUTION
Sharp Edges Installation Hazard.
Can cause personal injury.
Wear gloves and safety glasses.
1. Position the securing clips as shown in Fig. 3.
CLIP
CLIP
M12813
Fig. 3. Position securing clips.
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
2. Make sure the humidifier housing is level, then position it in the opening so the
plastic tabs are in place on the lower sheet metal edge of the opening. Use pli-
ers, as necessary, to flatten cut edges. See Fig. 4.
3. Push in securing clips until completely seated.
4. Drill holes and install the three sheet metal screws on the top of the humidifier
housing. Secure the housing with the three remaining screws.
DUCT
LEVEL
SHEET METAL
SCREWS (4)
OPENING
TO AIR DUCT
PLASTIC
TABS (2)
M20204
DRAIN TUBING
Fig. 4. Installing humidifier on duct.
5. Reinstall the humidifier pad assembly in the humidifier housing.
IMPORTANT
Be sure to reconnect the water feed tube and ensure that the tube is not
pinched or kinked.
6. Hinge the cover in place and secure with the thumbscrew located at the bottom
of the cover.
9
69-1176—04
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
Connecting the Plumbing
Use hot or cold water and either hard or softened water in the humidifier.
1. Shut off the water.
CAUTION
Chemical Hazard.
Can cause personal injury or equipment damage.
Do not use any line connected to an air conditioner.
Do not use gas line.
2. Use the self-piercing saddle valve (included) to tap into the water supply line at
the location selected. See Fig. 5. If tapping into galvanized pipe, drain line and
pre-drill 3/17 in. tap for saddle valve. The saddle valve is not designed to regu-
late water flow. The valve is either open or closed.
IMPORTANT
To prevent debris from clogging the solenoid in-line filter, be sure to install the
saddle valve handle pointing toward the ceiling.
SCREW DRIVER
WATER LINE
M20175
Fig. 5. Installing the saddle valve.
3. Use 1/4 in. (6 mm) OD tubing and connect the saddle valve to the inlet side of
the solenoid valveon the humidifier (see Fig. 6).
a. Place the brass compression nut over the tubing.
b. Install brass insert into end of tubing.
c. Slide the plastic compression ring over the tubing. (Discard copper com-
pression ring provided with valve.)
69-1176—04
10
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
NOTE: To prevent leaking, use plastic (Delrin) sleeve rings with plastic tubing. Use
copper sleeve rings only with copper tubing.
d. Insert the tubing into the solenoid valve fitting and support the valve while
tightening the compression nut.
NOTE: Do not over-tighten the compression nut. Moderate tightness prevents
leaking.
e. Repeat steps a. through d. for solenoid valve fitting.
f. Secure tubing with clamps provided.
BRASS COMPRESSION NUT
PLASTIC
COMPRESSION RING
BRASS INSERT
M20176
Fig. 6. Installing feed tubing.
4. Connect a 1/2 in. (13 mm) drain tube to the humidifier drain fitting and run to the
floor drain (see Fig. 7).
a. Slide the drain clamp over the tubing.
b. Push the tubing over the drain nipple on the humidifier.
c. Hand-tighten the clamp around the tubing to secure the humidifier drain.
d. Fasten the drain tubing (can use duct tape) along the route to prevent move-
ment and ensure downward slope for correct drainage.
NOTE: Cut tubing to correct length so the tubing terminates at the drain.
11
69-1176—04
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
M20177
Fig. 7. Installing the drain tubing.
Installing the Sail Switch
Adapting Switch to Air Flow Direction
The S688A Sail Switch has two counterbalancing springs in place as shown in Fig 8.
These springs offset the effect of gravity for air flow direction.
IMPORTANT:
Do not use the sail switch with both springs attached. Be sure to select air
flow direction and remove spring(s) not required for installation.
69-1176—04
12
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
UP
M3014
Fig. 8. Adapting sail switch to air flow direction or mounting position.
•
Vertical downward air flow: Leave the spring in place that is attached to the
bracket marked Down. Remove the spring that is attached to the bracket marked
Up.
•
•
Vertical upward air flow: Leave the spring in place that is attached to the bracket
marked Up. Remove the spring that is attached to the bracket marked Down.
Horizontal air flow: Remove both springs.
1. Mount the template (provided with the sail switch) at the desired location.
NOTE: Be sure the arrow (indicating air flow) points in the correct direction.
a. For horizontal mounting, level the long dimension shown on the template.
b. For vertical mounting, plumb the long dimension.
2. Cut the hole (indicated on the template) in the ductwork.
3. Center punch the screw holes indicated and drill out with a 1/8 in. (13 mm) drill.
4. Attach the sail to the switch as shown in Fig 9.
13
69-1176—04
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
– LOOSEN SETSCREW
– INSERT SAIL CORD
– TUCK CORD INTO TAB SLOTS
– TIGHTEN SETSCREW
SAIL
M31017
Fig. 9. Attaching sail to switch.
5. Press together the sides of the wire loop. Insert the sail into the duct. (When in
the Off position, the sail should point into the direction of airflow as shown in
Fig.10.)
M20178
Fig. 10. Inserting sail switch in direction of airflow.
69-1176—04
14
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
6. Secure the switch by using the sheet metal screws provided.
7. After wiring, snap on the cover.
Installing the Humidistat
Installing on Mounting Duct
1. Apply the template to the duct location chosen for the humidistat. Make sure the
template is level before drilling the holes.
2. Refer to the template (provided with the H8908 Humidistat Installation Instruc-
tions) to drill the control assembly opening and mounting holes for the H8908.
3. Remove the H8908 case from the base.
4. Position the foam gasket on the H8908 base.
5. Position the base on the duct with the arrow up.
6. Secure the base to the duct using the four
1 in. (25 mm) mounting screws provided with humidistat.
7. Connect the low-voltage wires to the leads and replace the H8908 case. See
Fig. 11.
NOTE: For wall mounting instructions, see the H8908 Installation Instructions.
HUMIDISTAT BASE
REAR OF HUMIDISTAT
WIRE SLOT
HUMIDISTAT WIRES
M20179
Fig. 11. Humidistat base and rear view.
15
69-1176—04
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
WIRING
CAUTION
Hazardous Voltage.
Can cause personal injury or equipment damage.
Disconnect power supply before installing or servicing equipment.
IMPORTANT
All wiring must comply with applicable local code, ordinances and regula-
tions.
Wire the humidifier solenoid valve, sail switch, humidistat and transformer.See Fig. 12.
HUMIDISTAT
SAIL
SWITCH
OUTDOOR
HUMIDITY
SETTING
15%
20%
25%
TEMPERATURE
-20 ¡F
-10 ¡F
¡F
+10 ¡F
-
3
0
¡
C
-25 ¡C
-20 ¡C
-10 ¡C
-5 ¡C
0
30%
35%
40%
Humidity Control
Régulateur d'hum
+20
¡F
O
v
e
r
2
0
¡
F
Over
0
¡C
idité
HUMIDIFIER
SOLENOID
VALVE
BLACK
WHITE
WHITE
M20205
Fig. 12. Wiring the controls.
1. Run the two-strand thermostat wire from the humidifier to the humidistat, and
from the humidistat to the sail switch.
2. Cut lengths of thermostat wire to reach between components, leaving adequate
wire at both ends for connections.
NOTE: Humidistat and sail switch can be wired in any order.
3. At the humidifier, connect the black and white conductors to the two yellow
humidifier wires. (The red wires from the humidifier are not used.)
4. At the humidistat, connect both black conductors to the two humidistat terminals.
Use a wire nut to connect together the two white conductors.
5. At the sail switch, connect the black and white conductors to the Com and NO
sail switch terminals (NC terminal is not used).
69-1176—04
16
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
TESTING HUMIDIFIER OPERATION
Checklist
Humidifier is level.
Control wiring was reviewed using circuit diagram.
Humidifier is plugged in.
Feed line has no kinks.
Drain line slopes continuously down and ends at floor drain.
Water hose inside humidifier is connected to PerfectFlow™ water distribution tray.
After installation use the following steps to check the humidifier operation:
1. Turn on the power and the water supply
2. Turn the H8908 Humidistat to On and turn on the heat by setting the thermostat
to 10ºF (6ºC) above room temperature.
IMPORTANT
The furnace blower must be on to activate the humidifier.
3. Make sure that water is flowing out of the drain hose. If water does not flow, see
Troubleshooting Your Humidifier section.
4. Check for leaks.
5. Reset the thermostat and H8908 Humidistat to a comfortable setting for auto-
matic operation.
Controlling Your Humidity Settings
Your H8908 Humidistat controls your humidifier.
•
•
Choose the humidity control setting using the combination of relative humidity/
outdoor temperature setting scale on your humidity control dial.
Match the dial setting to the outdoor temperature to optimize the humidity level
while reducing the moisture condensation on your windows. See Table 2 to adjust
the humidity control to the recommended setting.
NOTE: As the outside temperature drops, a lower humidity setting is recommended
to accommodate dewpoint effects. These settings should reduce the accumu-
lation of moisture and ice on windows and other areas of the home.
•
Adjust the humidity control setting to adjust for indoor activities such as cooking,
showering and clothes drying, which can cause excessive levels of humidity that
can accumulate moisture on your windows.
NOTE: If these activities persist for more than a few hours, set the humidity control to
the lowest setting to turn off the humidifier. If the condition does not improve,
ventilate your home to remove the moisture.
17
69-1176—04
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
Table 2. Setting Your Humidistat.
When Outside Temperature is:
-20°F (-29°C)
Use This Control Setting:
15
20
25
30
35
40
-10°F (-23°C)
0°F (-18°C)
+10°F (-12°C)
+20°F (-7°C)
Above 20°F (-7°C)
69-1176—04
18
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
MAINTAINING YOUR HUMIDIFIER
A regular maintenance program prolongs the life of your humidifier and makes your
home more comfortable. The frequency of cleaning depends on the condition of your
water.
You can use either hard or soft water in your humidifier, but hard water mineral
deposits are more difficult to clean than soft water deposits.
Use the following procedure to clean your Honeywell humidifier.
WARNING
Serious Personal Injury Hazard.
Can cause electrical shock and injury from moving parts.
Disconnect power and shut off water supply before removing cover.
IMPORTANT
Never oil any part of the humidifier.
Every 1 to 3 Months (Depending on Water Quality)
1. Disconnect the power and turn off the humidifier water supply.
2. Remove the humidifier cover by unplugging the connector and loosening the
thumb screw. Grasp the cover near the bottom and pull toward you. See Fig. 13.
3. Remove the humidifier pad assembly from the humidifier by grasping the top of
the tray and pulling it toward you.
4. Lift the tray off the pad.
5. Gently pinch the water nozzle catches inward until you can lift the water nozzle
off the tray.
6. Carefully remove any mineral deposits from the tray and frame. Be sure the
frame drain hole has nothing blocking it.
FEED TUBE NOZZLE
WATER
DISTRIBUTION TRAY
HUMIDIFIER
PAD ASSEMBLY
HUMIDIFIER
HOUSING
COVER
ASSEMBLY
THUMB
SCREW
M12809
Fig. 13. Cleaning your humidifier.
19
69-1176—04
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
7. Disconnect the drain hose from the drain fitting on the bottom of the humidifier
housing.
8. Clean the drain fitting, if necessary.
9. Bend the drain hose to loosen any mineral deposits.
10. Flush the drain hose with pressurized water (a running tap) to clean the hose.
11. Reattach the drain hose to the drain fitting.
12. Snap the water nozzle back on the tray.
13. Be sure the marked end of the pad is facing up. Place the tray on the new pad.
14. Place the humidifier pad assembly in the humidifier housing. Be sure the water
feed tube is placed in the guide slots.
15. Replace the humidifier cover.
16. Verify the humidifier operation by following the steps in the Checking Your
Humidifier for Correct Operation section.
CHECKING YOUR HUMIDIFIER FOR CORRECT
OPERATION
After winter startup or servicing, use the following steps to check your humidifier
operation:
1. Turn on the humidifier power and water supply.
2. Turn the humidistat to its highest setting and set the thermostat to 10°F (6°C)
above the room temperature.
3. Observe that water is flowing out of the drain hose.
NOTE: The furnace blower must be running to activate the humidifier.
4. Reset the thermostat and humidistat to a comfortable setting for automatic
operation.
69-1176—04
20
TROUBLESHOOTING YOUR HUMIDIFIER
Table 3. Troubleshooting Humidifier
Problem
What to look for
What to do
Water leakage
Leaking joints.
Shut off water.
Tighten connections.
Brass tubing
inserts
Verify that brass tubing inserts are used.
Saddle valve
leaking.
Verify rubber gasket is installed on saddle
valve.
No water to drain.
Electrical
Verify control circuit wiring.
Check all connections.
Humidistat
Turn humidistat up and down and listen for
contact to click.
Humidifier
power
Verify that outlet has power.
Sail switch
Remove sail cover; turn on furnace fan and
listen for faint click.
Verify that sail can move freely in duct; check
sail switch instructions to trim sail, if
necessary.
Solenoid
After verifying other wiring components, turn
on furnace fan, turn humidistat up and down,
and listen for solenoid to click.
Plumbing
Verify plumbing connections.
Check for kinks.
Saddle valve Verify that Saddle Valve needle pierces
water line, and has been backed out so that
the valve is open.
Humidifier
Remove cover and verify that water flows
into distribution tray.
Drain tubing
Verify no obstructions.
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
Table 3. Troubleshooting Humidifier (Continued)
Problem
What to look for
What to do
Low humidity
Furnace
blower not
•
Reset circuit breaker or check for blown
fuse.
operating.
•
•
•
•
Check that the furnace power is on.
Check all external wiring connections.
Check the humidity control setting.
Call a professional heating contractor.
Rapid air
changes.
•
•
Keep doors and windows closed.
Close fireplace damper when not in use.
Drafts (cold air • Keep exhaust fan running time to a
is dry and is an
added load to
the humidifier).
minimum.
Seal around doors and windows.
•
•
•
High humidity
Condensation
on walls.
Turn off humidity control and water until
condensation is completely evaporated.
Heavy
condensation
on windows.
Turn humidity control down low enough to
eliminate condensation caused by
moisture from bathing, mopping, cooking,
etc. If moisture persists, more ventilation
is needed.
69-1176—04
22
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
23
69-1176—04
HE360A,B POWERED FLOW-THROUGH HUMIDIFIER
LIMITED ONE-YEAR WARRANTY
Honeywell warrants this product, excluding humidifier pad, to be free from defects in
the workmanship or materials, under normal use and service, for a period of one (1)
year from the date of purchase by the consumer. If, at any time during the warranty
period, the product is defective or malfunctions, Honeywell shall repair or replace it (at
Honeywell’s option) within a reasonable period of time.
If the product is defective, return it, with a bill of sale or other dated proof of purchase,
to the retailer where you purchased it.
This warranty does not cover removal or reinstallation costs. This warranty shall not
apply if it is shown by Honeywell that the defect or malfunction was caused by damage
which occurred while the product was in the possession of a consumer.
Honeywell’s sole responsibility shall be to repair or replace the product within the
terms stated above. HONEYWELL SHALL NOT BE LIABLE FOR ANY LOSS OR
DAMAGE OF ANY KIND, INCLUDING ANY INCIDENTAL OR CONSEQUENTIAL
DAMAGES RESULTING, DIRECTLY OR INDIRECTLY, FROM ANY BREACH OF
ANY WARRANTY, EXPRESS OR IMPLIED, OR ANY OTHER FAILURE OF THIS
PRODUCT. Some states do not allow the exclusion or limitation of incidental or
consequential damages, so this limitation may not apply to you.
THIS WARRANTY IS THE ONLY EXPRESS WARRANTY HONEYWELL MAKES ON
THIS PRODUCT. THE DURATION OF ANY IMPLIED WARRANTIES, INCLUDING
THE WARRANTIES OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR
PURPOSE, IS HEREBY LIMITED TO THE ONE YEAR DURATION OF THIS
WARRANTY. Some states do not allow limitations on how long an implied warranty
lasts, so the above limitation may not apply to you.
This warranty gives you specific legal rights, and you may have other rights which vary
from state to state.
If you have any questions concerning this warranty, please write to Honeywell
Customer Care, 1885 Douglas Drive, Minneapolis, MN55422. In Canada, write Retail
Products ON15-02H, Honeywell Limited/Honeywell Limitée, 35 Dynamic Drive,
Scarborough, Ontario M1V 4Z9.
Automation and Control Solutions
Honeywell International Inc. Honeywell Limited-Honeywell Limitée
1985 Douglas Drive North
Golden Valley, MN 55422
yourhome.honeywell.com
35 Dynamic Drive
Toronto, Ontario M1V 4Z9
Printed in USA
® U.S. Registered Trademark
© 2009 Honeywell International Inc.
69-1176—04 T.W. Rev. 12-09
|