XLS-278 and XLS-270
Manual Pull Stations
S
Y
S
T
E
M
SPECIFICATION DATA
FEATURES
·
Single stage double action XLS-278 features a rugged
Lexan housing
·
·
XLS-270 models have traditional familiar appearance
XLS-270 models are available for one stage (GA),
two stage (pre-signal), and double action
·
·
·
·
·
·
·
·
·
Break glass operation on XLS-270 models
Intelligent device with integral microprocessor
Non-volatile memory
Automatic device mapping
Electronic addressing
Stand-alone operation
Diagnostic LEDs
Designed for high ambient temperature operation
Designed to ISO 9001 standards
DESCRIPTION
The integral microprocessor built into each Signature Series
station provides four important benefits: Self-diagnostics and
History Log, Automatic Device Mapping, Stand-alone
Operation and Fast, Stable Communication.
The XLS-270 and XLS-278 series Manual Pull Stations are
part of Honeywell's Signature Series system. The XLS-270
Fire Alarm Manual Pull Stations feature a "teardrop" shape.
They are made from die-cast zinc and finished with red epoxy
powder-coat paint complemented by aluminum colored
stripes and markings.
Self-Diagnostics and History Log:
Each Signature Series manual station constantly runs self-
checks to provide important maintenance information. The
results of the self-check are automatically updated and
permanently stored in the station's non-volatile memory. This
information is accessible for review any time at the control
panel, PC, or by using the SIGA-PRO Signature
Program/Service Tool.
With positive pull- lever operation, one "pull" on the station
handle breaks the glass rod and turns in a positive alarm,
ensuring protection plus fool-proof operation. Pre-signal
models (XLS-270P) are equipped with a general alarm (GA)
key-switch for applications where two-stage operation is
required. The "up-front" highly visible glass rod discourages
tampering.
The information stored in the station's memory includes:
- Station serial number, address, and station type.
- Date of manufacture, hours of operation, and last
maintenance date.
Honeywell's double action single stage XLS-278 station is a
contemporary style station made from durable red colored
Lexan. To initiate an alarm, first lift the upper door marked
"LIFT THEN PULL HANDLE", then pull the alarm handle.
EN0C-0741 0599R2-MA
XLS-270 AND XLS-278 MANUAL PULL STATIONS
SPECIFICATIONS
Models:
XLS-270: One stage fire alarm station; English markings
XLS-270P: Two stage (pre-signal) fire alarm station;
English markings
XLS-278: Double action, one stage fire alarm station;
English markings
Addressing Requirements:
XLS-270/270F/270B: 1 module address
XLS-270P/270PB:
XLS-278:
2 module addresses
1 module address
Operating Current:
XLS-270/270F/270B:
Standby: 250mA
Activated: 400mA
XLS-270P/270PB:
Standby: 396mA
Activated: 680mA
XLS-278:
Standby: 250mA
Figure 1: XLS-270L
Activated: 400mA
Construction and Finish:
XLS-270xx:
Die-cast zinc; red epoxy with aluminum markings
XLS-278:
Lexan, red with white markings
Type Code:
Factory set
Operating Voltage:
15.2 to 19.95V dc (19V dc nominal)
Environmental Limits:
Temperature: 32° to 120°F (0° to 49°C)
Humidity: 0 to 93% rh
LED Operation:
On-board green LED: Flashes when polled
On-board red LED: Flashes when in alarm/ active
Both LEDs: on steady when in alarm (stand-alone)
Compatibility:
Figure 2: XLS-278
Use with Signature Loop Controller
Accessories:
276-GLR: 20 glass rods; for XLS-278 only
27193-11: Single Gang Surface mounting box
for XLS-270xx models only
276B-RSB: Surface mounting box, red for XLS-278 only
3
EN0C-0741 0599R2-MA
XLS-270 AND XLS-278 MANUAL PULL STATIONS
Comfort from Experience
European Centre of Excellence
Home and Building Control
Honeywell Inc.
Honeywell Plaza
P.O. Box 524
Minneapolis MN 55408-0524
Home & Building Control
Honeywell GmbH
Honeywellstrasse
63477 Maintal 1
Germany
Fire Solutions
Lovelace Road, Southern Industrial Area
Bracknell, Berkshire, RG12 8WD
United Kingdom
EN0C-0741 0599R2-MA
4
|
Grizzly Kitchen Utensil T25225 User Manual
Haier Freezer DW 40L626 User Manual
Haier Microwave Oven MWG7036RW B User Manual
Havis Shields Automobile Parts C TCB 34 User Manual
Hotpoint Clothes Dryer ACC9 BF7 User Manual
HP Hewlett Packard Fax Machine 820 RF User Manual
HP Hewlett Packard Network Card 3C900 User Manual
Husqvarna Lawn Mower Accessory I0807213 User Manual
Hyundai Flat Panel Television Q421H User Manual
Ice O Matic Ice Maker EF 450 Series User Manual